Cleanvent Dirt Separator CVD
Dirt Removal from Heating / Chilled Water Systems
Sludge and dirt in heating and chilled water systems can be the cause of major problems such as pump failure, corrosion and energy loss.
The Cleanvent is used to remove dirt. Installed on the return pipe in the system the Cleanvent will eliminate all types of dirt particles from heating and chilled water systems.
Introduction
Cleanvent - The Clean Solution – A dirt free water system.
Problems arising with dirt in water systems
Dirt Removal
Sludge & dirt particles can be the cause of major problems such as pump failure, corrosion and energy loss in
Heating & Chilled Water Systems.
The Solution
The Cleanvent is used to remove dirt. Installed on the return pipe in the system the
Cleanvent will eliminate all types of dirt particles from heating and chilled water systems down to 10 microns.
Features
- Greatly reduced commissioning times after initial fill.
- Longer system life (dirt elimination)
- Low-pressure drop
- Bi-directional flow
- Max.temp. 110 c
- Max. Working pressure 14 bar
- Tested to 21 bar
- Standard carbon steel shell (stainless on request)
- Large collector ensures that flushing is only required periodically
- Can be flushed while fully operational (no need to shut down)
- An internal stainless steel concentrator to aid removal of dirt.
Cleanvent (CVD) location Click link for further deatils
This unit must be installed in the return pipe of the system.
Commissioning
The Cleanvent requires no special commissioning .
Maintenance will be required to remove trapped dirt and sludge. Opening the ball valve at the bottom of the
unit does this. The valve may be opened while the system is under pressure.
Scalding is a danger at high pressures and temperatures. Ensure that the water is safely piped to drain
before opening the valve.
The system pressure will flush the dirt out. Leave the valve open until the collected dirt has been flushed
out, repeat this operation every few days. Once the water is clear it may be possible to drain every 6 months
or so depending on the size and age of the system.
Dirt separators can only remove dirt that is circulating.
Flanges
All flanges are drilled to BS 4504 PN16 as standard. Plain ends and other flange rating are available on
request.
Drain valve
All models are supplied with a ball valve for draining the collected dirt and sludge.
|